1721v-wsk70_persp2.jpg
1721v-wsk70_persp2.jpg 1719v-wsk30_persp2.jpg 1720v-wsk40_persp2.jpg

WSK

Wound-Primary Current Transformers for Indirect Measurement of Sinusoidal AC up to 100 A

As opposed to bushing-type current transformers, wound-primary current transformers have 4 screw terminals. Primary and secondary current are both connected by means of terminals. Wound-primary current transformers are suitable for low amperage current for which bushing-type current transformers cannot be used.

Thermal continuous current rating Icth: 100% IN
Thermal short-time current rating Ith: 60 x IN, 1 Sek.
Max. operating voltage Um: 0,72 kV
Insulation test voltage: 3 kV Ueff, 50 Hz, 1 Min.
Nominal frequency: fN: 50 Hz
Insulation class: E (120°C)

DesignationPrimary current(A)VAOrdernumber (Sec. 5 A)Ordernumber (Sec. 1 A)Dimensions (B x H x T)
WSK 30151719V00101719V101061 x 75,5 x 35 mm
WSK 302,551719V00201719V102061 x 75,5 x 35 mm
WSK 30551719V00301719V103061 x 75,5 x 35 mm
WSK 301051719V00401719V104061 x 75,5 x 35 mm
WSK 301551719V00501719V105061 x 75,5 x 35 mm
WSK 302051719V00601719V106061 x 75,5 x 35 mm

WSK 401101720V00101720V101071 x 85,5 x 45 mm
WSK 402,5101720V00201720V102071 x 85,5 x 45 mm
WSK 405101720V00301720V103071 x 85,5 x 45 mm
WSK 4010101720V00401720V104071 x 85,5 x 45 mm
WSK 4015101720V00501720V105071 x 85,5 x 45 mm
WSK 4020101720V00601720V106071 x 85,5 x 45 mm
WSK 4025101720V00701720V107071 x 85,5 x 45 mm
WSK 4030101720V00801720V108071 x 85,5 x 45 mm
WSK 4040101720V00901720V109071 x 107 x 55 mm

WSK 70.630101721V0080 1721V108061 x 85,5 x 136 mm
WSK 70.640101721V0090 1721V0090 61 x 85,5 x 136 mm
WSK 70.650101721V01001721V110061 x 85,5 x 136 mm
WSK 70.660101721V01101721V111061 x 85,5 x 136 mm
WSK 70.675101721V01201721V112061 x 85,5 x 136 mm
WSK 70.680101721V01301721V113061 x 85,5 x 136 mm
WSK 70.6100101721V01401721V114061 x 85,5 x 136 mm