PROFiTEST MF TECH 0105-Set
PROFiTEST MF TECH 0105 Set for Testing the Effectiveness of Protective Measures at Stationary Electrical Systems After Periodic Testing, Especially for the Fulfillment of DGUV Regulation 3
PROFiTEST MF TECH 0105 Set with PROFiTEST MF TECH, voltage tester and defined accessories for testing the effectiveness of protective measures at stationary electrical systems in accordance with testing standard EN 50110-1 (DIN VDE 0105-100). Measuring category: 300 V CAT IV / 600 V CAT III
- Context-sensitive color graphic display
- Measuring and test sequence – easy setup of the system structure / measuring and storage / report generation
- Preconfigured and user programmable test sequences for testing electric systems quickly
- Storage concept for up to 50,000 data records
- Testing of all up-to-date AC/DC sensitive RCDs, RDC-DDs and RCMBs
- User safety thanks to PE detection when using finger contact
- Forward-looking connectivity
- Defined accessories for special measuring tasks
- Broad-range measuring device for all alternating and 3-phase electrical systems with voltages from 65 to 500 V and frequencies of 15.4 to 420 Hz
- Loop and line impedance measurement with DC bias magnetization
- Measurement of insulation resistance using nominal voltage, with variable or rising test voltage
- Low-resistance measurement with automatic polarity reversal
- Testing of residual current devices and special RCCBs (selective S, SRCDs, PRCDs, Schukomat, Sidos, types G/R, AC, A, A-EV, F, F-EV, B, B+ and B-MI)
- Testing of RDC-DDs per IEC 62955 and RCMBs per IEC 62752
- Testing of RCCBs in IT systems
- Measurement of earth resistance (mains operation)
- Standards-compliant testing of charging stations per IEC 61851-1 in combination with a suitable test adapter
- Automatic test sequence function
- USB port
- Push-print function – transmission of the measured value after measurement
- Defined accessories for special measuring tasks
- Intuitive user prompting with help function which provides support for pending measuring tasks
- All decisive measuring functions can be quickly selected with the rotary switch
- Especially well-suited for mobile use, even at construction sites and in industrial environments, thanks to the compact, impact-resistant housing with integrated rubber protector
- Also suitable for international use thanks to extensive setting options for language etc.
- 4-wire measuring method – no compensation of the measurement cables is required
Testing of the effectiveness of protective measures at stationary electrical systems for periodic testing per EN 50110-1 (DIN VDE 0105-100) and other country-specific standards.
1 PROFiTEST MF TECH
1 Earthing contact plug insert (country-specific)
1 Two-pole measuring adapter
1 Cable for expansion into a 3-pole adapter (PRO-A3-II)
2 Alligator clips
1 Neck strap
1 Set of rechargeable batteries (Z502H)
1 Charger (Z502R)
1 Condensed operating instructions
1 Supplementary sheet with safety information
1 DAkkS calibration certificate
1 USB interface cable
1 METRAVOLT 12D+L
1 SORTIMO plastic system case with insert
1 IZYTRONIQ Business Professional software
1 IZYTRONIQ coupon for 12-month cloud subscription